Prism

Ask

California

Disinfection.

22 CCR 60353

Source text

12 segments

22 CCR 60353

22 CCR 60353

§ 60353. Disinfection.

(a)

All disinfection unit processes where chlorine is used as the disinfectant shall be provided with the following features for uninterrupted chlorine feed: Automatic residual control of chlorine dosage, automatic measuring and recording of chlorine residual, and hydraulic performance studies may also be required.

(1)

Standby chlorine supply,

(2)

Manifold systems to connect chlorine cylinders,

(3)

Chlorine scales, and

(4)

Automatic devices for switching to full chlorine cylinders.

(b)

All disinfection unit processes where chlorine is used as the disinfectant shall be provided with one of the following reliability features:

(1)

Alarm and standby chlorinator;

(2)

Alarm, short-term retention or disposal provisions, and standby replacement equipment;

(3)

Alarm and long-term storage or disposal provisions;

(4)

Automatically actuated long-term storage or disposal provisions; or

(5)

Alarm and multiple point chlorination, each with independent power source, separate chlorinator, and separate chlorine supply.